Wenzhou Shuowei Electric Co., Ltd. is one of the most reliable manufacturers and suppliers of c-gis direct-acting vcb/isolation switch unit – 12kv-40.5kv in China, also supports customized service. Welcome to wholesale bulk advanced c-gis direct-acting vcb/isolation switch unit – 12kv-40.5kv in stock here from our factory. If you have any enquiry about quotation, please feel free to email us.
C-GIS Direct-Acting VCB/Isolation Switch Unit – 12kV-40.5kV

Products Description
What is a C-GIS direct-acting VCB/isolation switch integrated unit?
The C-GIS Direct-Acting Vacuum Circuit Breaker (VCB) / Isolation Switch Integrated Unit is a compact, sealed module that combines a vacuum circuit breaker and a disconnector (isolation switch) into a single, mechanically interlocked assembly – driven by a direct-acting mechanism. It is the core switching and isolation component of C-GIS (Cubicle-type Gas Insulated Switchgear) for 12kV – 40.5kV medium voltage distribution networks.
Unlike traditional designs where the breaker and disconnector are separate, this integrated unit uses a common direct-acting operating mechanism to sequence the breaker opening/closing and disconnector isolation in a predefined interlocked order. This eliminates additional space requirements, reduces mechanical complexity, and improves operational safety.
How does the direct-acting integration work?
The direct-acting mechanism transmits motion directly from the operating handle or motor to both the vacuum interrupter (for load breaking) and the disconnector (for visible isolation). The interlock ensures:
Disconnector can only operate when breaker is OPEN
Breaker can only CLOSE when disconnector is fully engaged
Earth switch interlock (optional third position)
Products Main technical parameters
| No. | Item | Unit | Technical Parameters |
|---|---|---|---|
| 1 | Rated Voltage | kV | 40.5 |
| 2 | Rated Frequency | Hz | 50 |
| 3 | Rated Current | A | 630/1250/1600/2000/2500 |
| 4 | SF6 Gas Rated Pressure (Gauge Pressure at 20°C)/For Gas-Insulated Switchgear | MPa | 0.04 |
| 5 | Rated Power Frequency 1min Withstand Voltage | - | - |
| 5.1 | - Isolation Gap | kV | 118 |
| 5.2 | - Phase-to-Phase/Phase-to-Ground | kV | 95 |
| 6 | Rated Lightning Impulse Withstand Voltage Peak (1.2/50μs) | - | - |
| 6.1 | - Isolation Gap | kV | 215 |
| 6.2 | - Phase-to-Phase/Phase-to-Ground | kV | 185 |
| 7 | Rated Short-Time Withstand Current | kA/s | 31.5/4 |
| 8 | Rated Peak Withstand Current | kA | 80 |
| 9 | Rated Short-Circuit Breaking Current | kA | 31.5 |
| 10 | Rated Short-Circuit Making Current | kA | 80 |
Products Dimension

Products FAQ
Q: What is C-GIS?
A: C-GIS (Cubicle-type Gas Insulated Switchgear) uses SF6 or clean air as insulation for compact size. This integrated unit is its core switching module.
Q: What does "direct-acting" mean?
A: One mechanism drives both the breaker and disconnector in sequence, with built-in mechanical interlock – no separate mechanisms or external linkages.
Q: What positions are available?
A: 3-position: CLOSE / OPEN / EARTH. 4-position: adds ISOLATE (visible isolation gap).
Q: Does this replace separate breaker + disconnector?
A: Yes. It combines both into one module, saving space and simplifying installation.
Q: Is motor operation available?
A: Yes, for SCADA integration (110/220V DC/AC).
Q: What standards does it meet?
A: IEC 62271-200, IEC 62271-100, GB/T 3906, GB/T 1984.
Hot Tags: C-GIS Direct-Acting VCB/Isolation Switch Unit – 12kV-40.5kV, China C-GIS Direct-Acting VCB/Isolation Switch Unit – 12kV-40.5kV manufacturers, suppliers, factory, Indoor H V Vacuum Load Break Switch, FN7 12 KV Indoor H V Load Breaking Switch With Fuse