24kV Indoor SF6 LoadBreak Switch

24kV Indoor SF6 LoadBreak Switch

24kV Indoor SF6 Switch-Disconnector FL(R)N36 Load Break Switch LBS and fuse combination appliance are designed for power stations and industrial electrical equipment. They are used for load control and line protection in 24kV power systems, handling various currents including load, closed-loop, and charging currents. The combined appliance can interrupt rated short-circuit currents, making it ideal for electrical equipment sets like ring network units and box-type substations.
Send Inquiry
Description

Wenzhou Shuowei Electric Co., Ltd. is one of the most reliable manufacturers and suppliers of 24kv indoor sf6 loadbreak switch in China, also supports customized service. Welcome to wholesale bulk advanced 24kv indoor sf6 loadbreak switch in stock here from our factory. If you have any enquiry about quotation, please feel free to email us.

 

24kV Indoor FL(R)N36 LoadBreak Switch LBS-SF6 Switch-Disconnector

Products Description

24kV Indoor SF6 Switch-Disconnector FL(R)N36 Load Break Switch LBS and fuse combination appliance are designed for power stations and industrial electrical equipment. They are used for load control and line protection in 24kV power systems, handling various currents including load, closed-loop, and charging currents. The combined appliance can interrupt rated short-circuit currents, making it ideal for electrical equipment sets like ring network units and box-type substations.


These devices are particularly well-suited for urban residential power distribution, small secondary substations, switch offices, industrial and mining sites, large shopping malls, airports, subways, hospitals, stadiums, and similar locations.
The product meets standards GB3804, GB16926, IEC 60265-1, and IEC60420.

 

Products Parameter

 

No. Parameter Unit FLN36-24 FLRN36-24 Notes
1 Rated Voltage kV 24 24  
2 Rated Frequency Hz 50 50 (Typo corrected)
3 Rated Current A 630 1250  
4 Rated Insulation Level        
  - Power Frequency Withstand Voltage (1 min)        
  - Phase-to-Phase kV 50 50  
  - Phase-to-Earth kV 50 50  
  - Fracture kV 60 60  
  - Lightning Impulse Withstand Voltage (Peak)        
  - Phase-to-Phase kV 125 125  
  - Phase-to-Earth kV 125 125  
  - Fracture kV 145 145  
5 Auxiliary Circuit 1 min Power Frequency Withstand Voltage V 2000 2000  
6 Rated Thermal Stability Current (Duration)        
  - Main Switch (3s/2s) kA 20 20  
  - Earthing Switch kA 20 20  
7 Rated Short-Circuit Making Current kA 12.5 12.5  
8 Rated Closed Circuit Breaking Current A 630 630  
9 Rated Active Load Breaking Current A 630 630  
10 Rated Cable Charging Breaking Current A 10 10  
11 Rated Transfer Current A 1700 1700  
12 Expected Short-Circuit Breaking Current kA 50 50  
13 Mechanical Life Times 2000 2000  
14 SF6 Gas Rated Pressure (20°C, Gauge) MPa 0.04 0.04  
15 SF6 Gas Max Pressure (20°C, Gauge) MPa 0.045 0.045  
16 Annual Leakage Rate %/Y 0.5 0.5  
17 Opening/Closing Synchronicity ms ≤3 ≤3  
18 Circuit Resistance μΩ ≤100 ≤100  

Fuse Rated Parameters

No. Rated Voltage (kV) Fuse Rated Current (A) Fuse Link Rated Current (A) Rated Breaking Current (kA)
1 24 40 6.3, 10, 16, 20, 25, 31.5, 40 40
2 24 100 50, 63, 80, 100 40
3 24 125 125 50

 

Products Features

Category Specification
Integrated Design Combines load switch, isolation switch, and grounding switch in one SF6-insulated sealed box (0.04–0.05 MPa pressure). Complies with "closed pressure system" standards.
Three-in-One Function Simultaneously fulfills load breaking, isolation, and grounding functions.
Safety Mechanisms - Natural interlock ensures only one position (closed/open/grounded) at a time.
- Insulated box includes a safety membrane for reverse pressure release.
Voltage Indication Built-in voltage indicator for operational monitoring.
Spring Mechanism Spring-operated for stable performance and reliability.
Arc Extinction - Rated transfer current breaking: 1400A.
- SF6 gas ensures superior arc quenching.
- Maintains breaking capability even at zero pressure.
Insulation Performance - SF6 gas provides excellent dielectric strength.
- Epoxy resin (APG) insulation box: high mechanical strength, large insulation margin.
Sealing & Leakage Annual SF6 leakage rate ≤0.5%.
Modular Design Compact structure, adaptable for diverse applications. Easy installation.
Remote Control Optional motorized mechanism enables "Three Remote" (remote monitoring, control, operation).

Products Operating Mechanism

 

1. Switch switching is achieved through an operating mechanism. The mechanism spring stores energy in advance, and during operation (manually or electrically), it releases energy after passing through the dead point, driving the switch to close or open the contacts. Therefore, the opening and closing speed of the switch is determined by the characteristics of the operating mechanism and is independent of the operator's speed.
2. Depending on whether there is a fuse, K-type or A-type operating mechanisms can be selected

 

 

Products Usage Environment

 

No. Parameter Specification Notes
1 Ambient Temperature Upper limit: +40℃
Lower limit: -15℃
Operating temperature range
2 Environmental Humidity Daily average relative humidity ≤95%
Monthly average relative humidity ≤90%
Humidity conditions
3 Altitude Maximum installation altitude: 2000m Elevation limit
4 Seismic Resistance Maximum earthquake intensity: 8 degrees Seismic design standard
5 Air Quality Requirements No severe pollution including:
- Dust/smoke
- Chemical corrosives
- Flammable gases
- Gasoline/salt agents
Clean air environment
6 Special Requirements Consultation with manufacturer required for different conditions or other requirements Custom solutions available for non-standard environments or needs

 

Products Packings

 