Don't you need 1250A type C casing for your 35KV inflator?
The 35kV C-type bushing (1250A)https://www.suvell.com/mv-switchgear-component/bushing-busbar/gas-insulated-switchgear-bushing.html is a key insulating component in gas-insulated switchgear (GIS), mainly used to connect high-voltage conductors to the cabinet body to ensure insulation and sealing performance. The following is a systematic introduction to this product:

1. Basic structure and types
C-type design: Generally refers to the "insertion type" or "conical connection" structure, which is convenient for installation and maintenance and is suitable for compact gas-filled switchgear.
Core materials: High-performance insulating materials such as epoxy resin or silicone rubber are adopted, featuring excellent dielectric strength and mechanical stability.
Conductor specification: Rated current 1250A, the cross-sectional area of the conductor needs to meet the requirements of long-term current-carrying capacity and short-term endurance (such as 31.5kA/4s).
2. Key performance parameters
Rated voltage: 35kV (power frequency withstand voltage ≥70kV, lightning impulse withstand voltage ≥170kV).
Sealing performance: When used with SF6 gas, the leakage rate is ≤0.5% per year (in compliance with IEC 62271-200 standard).
Temperature range: -30℃ to +70℃ (Outdoor type needs to meet lower temperature requirements).
Partial discharge level: usually ≤10pC (tested at 1.2Ur).
3. Core Functions
Electrical insulation: Isolate high-voltage conductors from the grounded cabinet to prevent surface discharge.
Mechanical support: Fix the position of the conductor and withstand short-circuit electromagnetic forces (such as 80kA peak).
Air chamber separation: In coordination with the sealing ring, maintain the air chamber pressure (such as 0.04MPa gauge pressure).
4. Typical application scenarios
Gas-filled switchgear type: Suitable for modular GIS equipment such as ring main units and circuit breaker cabinets.
Installation method: Vertical or horizontal installation, commonly found at the connection between the cable room and the busbar room.
Compatibility: It can be integrated with plug-in lightning arresters and current transformers in design.
5. Precautions for Selection
Compatibility: It is necessary to match the interface of the cabinet manufacturer (such as ABB SafeRing/SaceAir, Siemens 8DJH, etc.).
Environmental grade: Indoor (IP3X) or outdoor (IP67) protection requirements.
Certification standards: Type tests such as GB/T 4109 and IEC 60137 must be passed.
6. Maintenance and testing
Routine inspection: Infrared temperature measurement (joint temperature rise ≤65K), SF6 gas pressure monitoring.
Life assessment: It is recommended to replace it every 20 years (the actual replacement cycle should be combined with the results of partial discharge tests).
Fault symptoms: Emergency treatment is required when there are creepage marks on the surface and the water content in the gas exceeds 300ppm.