Why Did Your Lightning Arrester Malfunction?

Sep 09, 2025

Leave a message

Analysis of Common Causes of Failures

Introduct Of Surge Arrester

Failures of arresters can generally be categorized into three main types: internal causes and external causes.

c41f6495a7d046c69972bad07fac4dd8

I. Internal Causes

1.Deterioration of Valve Plate Performance

Cause: The valve plate is the core component of an arrester, responsible for limiting overvoltage and absorbing energy.

Natural aging: Under long-term power frequency voltage and multiple overvoltage impacts, the valve plate gradually ages, resulting in degraded nonlinear characteristics and increased leakage current.

Insufficient energy absorption capacity: When subjected to excessive energy impacts beyond its design capacity (e.g., close-range lightning strikes, switching overvoltages), the valve plate may be damaged due to excessive energy absorption, often manifesting as explosion or cracking.

Manifestations: Increased leakage current, frequent operation of the counter, abnormal rise in shell temperature.

 

2.Sealing Failure

Cause: Poor sealing technology or aging of sealing rings allows moisture and water from the air to penetrate the interior.

Consequence: Reduced internal insulation strength, leading to internal creepage or partial discharge under operating voltage, ultimately resulting in insulation breakdown, internal arcing, and arrester explosion. This is one of the main causes of severe arrester failures.

u6480945233685096311fm253fmtautoapp138fJPEG

 

 

214323ygudyesq55ss6zqo

3.Voltage Equalizing Ring Detachment or Improper Design

Cause: Primarily applicable to high-voltage arresters. It can cause uneven voltage distribution, leading to premature aging or damage of some valve plates due to excessive voltage stress.

4.Loose Internal Connecting Components

Cause: Internal springs, wires, and other connecting components become loose due to vibration or heating, resulting in increased contact resistance and localized overheating.

 

 

 

II. External Causes

1.Overvoltage Impact Exceeding Withstand Capacity

Cause: Exposure to exceptionally strong lightning overvoltage or switching overvoltage, where the amplitude and energy exceed the arrester's maximum design capacity.

Manifestation: Typically leads to instantaneous explosion of the arrester.

2.Abnormal System Operating Conditions

Power Frequency Voltage Rise: Conditions such as neutral point displacement or single-phase grounding faults can cause voltage rise in non-fault phases, subjecting the arrester to prolonged voltage higher than its continuous operating voltage (Uc), accelerating valve plate aging.

Resonant Overvoltage: Ferroresonance in the system generates high-amplitude, long-duration overvoltages, causing the arrester to thermally collapse and explode due to excessive energy accumulation.

3.Installation and Connection Issues

Cause: Loose or poorly connected leads leading to overheating and burning of contact points; uneven mechanical stress during installation causing porcelain shell rupture.