What is an SF6 environmental protection gas density monitor?

The density monitor adopts spring tubes and bimetallic strips (temperature compensation) as the main sensing elements, which are used to control and monitor the density of gas in a closed container. It can display the gas density inside the equipment on site. When the density value reaches the set value, it will promptly issue alarm, lock and overpressure alarm signals. It can be widely applied to SF6 circuit breaker ring main units, gas-filled cabinets, environmental protection gas cabinets, pole-mounted switches and transformers, ensuring the safe operation of equipment.

It adopts a stainless steel casing and gas line connection parts, featuring an elegant appearance and a high protection level.
It adopts gold-plated contacts, featuring high breaking power and low contact resistance.
It adopts imported temperature sensing elements, featuring high precision and stable performance.
It adopts silver fiber and laser welding, and is sealed and leak detected by ammonia mass spectrometry to ensure sealing performance.
It adopts multiple interface connection methods and can be matched with various self-sealing valves, suitable for all kinds of SF6 and environmental protection gas cabinet equipment at home and abroad.
|
Parameter |
SpecificationandConditions |
|
Measuring Range |
Relative Pressure: -1.0 ~ 1.0 bar; Absolute Pressure: 0 ~ 2.0 bar |
|
Accuracy Class |
Class 1.5 (at 20°C); Class 2.5 (from -40°C to 60°C) |
|
Connection Thread |
M24 × 1.5 |
|
Operating Temperature |
-40°C to 60°C |
|
Relative Humidity |
≤95% |
|
Protection Class |
IP67 |
|
Shock Resistance |
300 m/s² |
|
Vibration Resistance |
20 m/s² |
|
Dielectric Strength |
AC 2000 V/min, 50/60 Hz |
|
Insulation Resistance |
≥100 MΩ |
|
Annual Leakage Rate |
≤1 × 10⁻⁹ bar·m³/s |
|
Contact Capacity |
AC/DC 250V, 50 VA / 30 W |
|
Maximum Operating Voltage |
AC 380 V |

Why is it needed?
SF6 and its eco-friendly alternatives are critical insulating mediums in high-voltage equipment. Their density directly determines the insulation capability.
Gas leakage leads to a decrease in density, which may cause equipment failure or even explosions. The density monitor, through continuous monitoring, acts as a "guardian" for the safety of power systems.